Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 05/13/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*/ 1) (YARD LINE TO FURNACE) |
| 05/09/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) GAS LINE NOT HOLDING PRESS "0" ON GAUGE, YOU NEED 10 POUND FOR MINIMUM IS MINUTES. WHILE INSPECTOR IS ON SITE 2) DEPTH AND INSTALLATION |
| 04/17/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NEED A TWO DIMENSIONAL PIPE DIAGRAM SHOWING GAS PIPING FROM METER TO APPLIANCES INCLUDING PIPE MEASUREMENTS 2) APPROX 90 PLUS FEET METER TO 3/4" LINE ENTERING THE HOUSE 30 PIPE IS TOO SMALL (175 DEMAND-111 DELIVERY AT HOUSE WALL YOU HAVE APPROX 150 PLUS FT OF) 4) NEED 1/4" PITCH FOR FT GAS FLUE |