Permit: T02CM01819

Parcel: 133160470

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/04/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
05/31/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*REGISTER BOXES AT ENTRY WAY NOT INSULATED INSULATE TOPS OF METAL BOXES ALSO. LEAVE A TILE OPEN AT EACH SUPPLY DIFFUSER. ON FINAL CONDENSATE NOT SIZED PROPERLY. TERMINATE TO AN APPROVED LOCATION. PROVIDE OUTSIDE AIR VENTS ON AC EQUIPMENT COVER CANVAS CONNECTOR. PROVIDE TRAPS ON CONDENSATE DRAIN LINES.