Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/23/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* 1.) LABEL CIRCUIT BREAKER FOR A/C UNIT 2.) A/C UNIT OVERFUSED AT 30 AMP 25 AMP. IS MAX FUSE SIZE. 3.) PROVIDE SCREWS WHERE VENT CONNECTS TO WATER HEATER. RECALL FOR INSPECTION. |