Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM01788
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
10/29/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) USE ALL 16D COMMON NAILS IN PA'S 2) POST CAPS AND BASES PER PLAN NAILED PER SIMPSON SPECS 3) NEED SHOWN ON PLANS SHEAR TRANSFER AT GABLE ENDS, SHEATH UP TO UNDERNEATH OF ROOF DECK, OR SUPPLY PLAN NOTE FOR TRANSFER | |
10/25/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000* | |
10/24/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) EXTERIOR CLIP NAIL PER SHEAR SCHEDULE 2) NAIL ALL PAS 3) ALL SHEAR TRANSFER ARE ON DETAIL 12/D2 CAN BE INSTALLED ON THE INSIDE 4) NEED HANGERS SPEC FOR HEADER AT FIREPLACE 5) CROSS BRACE TRUSS AT MID SPAN EACH END AND 25' ON CENTER 6) NEED BRACING DETAIL FOR FRONT PORCH ARCH 7) NEED TRUSS DRAWINGS 8) INSTALL ALL LATERAL BRACES ON TRUSS DRAWINGS | |
10/21/2002 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) GARAGE ROOF AND CLIP OK |