Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM01781
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 11/22/02 AT 9:15AM OK CABLE DROP & TEMP SERVICE "OWNERS PANEL" ONLY. | |
11/06/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*1.) NO TEMP SERVICE SET UP TEMP POLE FOR SITE ALREADY APPROVED. 2.) FINISH TORQUEING METER SECTIONS AS PER MANFACTURS INSTRUCTURE. 3.) ADDRESS ON SERVICE DO NOT MATCH PERMIT PLEASE CORRECT. 4.) INSTALL GROUNDING ELECTRODE CONDUCTOR SIZED PER PLANS. |
|
11/04/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0235* 1.) NEED SERVICE PNLS. OPEN TO INSPECT GROUNDING. |
|
10/31/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1.) ADDRESSING MISSING 2.) UFER JUST TERMINATED TO ENCLOSURE NEEDS TO TERMINATE WITH NEUTRAL. 3.) PLAN SHOWS 2 SETS OF 3 - 350 MCM'S ONLY ONE RISER INSTALLED. |