Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM01781
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK WALLS. | |
12/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARENCE ABOUT SERVICES PHONE & CABLE. 2.) MAINTAIN FIREWALL PENITRATION AND MANUFACTURE RATINGS. 3.) FINSH PREVIOUS INSPECTION AS DISCUSSED. |
|
12/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*#101,102 SUBJECT TO PAPERWORK FROM MANUFACTURE FOR BOXES FOR PLACEMENT IN FIRE WALL FOR MEMBRANCE PENITRATIONS. | |
12/04/2002 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - Ri canceled | |
12/03/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*) MISSING GROUND DEVICE IN 3/O BOX. 2.) PLEASE BE AWARE OF ARC FAULTS REQUIREMENTS FRO BEDROOMS 3.) NO OTHER OUTLETS ALLOWED ON KITCHEN APPLIANCE CIRCUITS. 4.) WHERE IS GFI AT FRONT ENTRANCES 210-52 (E) 5.) FINISH PREVIOUS INSPECTIONS. |
|
11/27/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* 1.) AN APPROVED CONNECTOR IS NEED AT PANEL, JUNCTION BOXES, 2.) WE HAVE CONDUCTOR OVER FILL FOR BOXES 3.) MAIN FIRE WALL SEPERATION. 4.) WE HAVE TORN CUT CABLE INSULATION. 5.) MAINTAIN OUTLET SPACING PER 210-52. 6.) BOXES TO HAVE CABLES SUPPORTED WITHIN 12". |