Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
The login landing page when selecting 'View' is still occurring and is still pending further investigation.
Inspection Status: Denied
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/17/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1) BLOCK NORTH DINING ROOM DUCT BOOT 2) MOVE BLUE WIRES FROM TOP OF CAN LIGHT IN KITCHEN 3) PLAN CALLS FOR 2ND GFI IN EAST BATH |