Permit: T02CM01723

Parcel: 13822013A


Addresses:

941 W COVENTRY PL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/06/2002 FRAMING Approved IVRS - Inspection 0000*
06/03/2002 FRAMING Denied IVRS - Inspection 0935*/ 1) A REFEE HAS BEEN ASSESED FOR THIS INSPECTION, MULTIPLE INSPECTIONS HAVE BEEN MADE WITH NO PROGRESS ON JOB SITE
05/31/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) NAIL PROTECT LAUNDRY VENT 2) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT LAUNDRY VENT (ROOFING PAPER) 3) MISSING 2 JOIST'S IN MASTER BEDROOM TO SUPPORT HVAC ON ROOF 4) MISSING BOLTS AT TRIPPLE 2 X 10 BEAM 5) DWV'S FAILED WATER TEST 6) RED HEADS NOT PROPERLY INSTALLED AT MASTER BATH AREA PULLED OUT BY HAND CHECK ALL RED HEADS 7) NOT 3050 GAS PRESSURE TEST NOT ON PERMIT IN IVR
05/28/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) NO PLANS PERMIT ON SITE 2) NEXT FAILURE WILL RESULT IN A RE-FEE 3) PLUMBING NOT READY