Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000* |
| 11/05/2003 |
ELECTRIC - UFER |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK UFER AT SERVICE, INSTALL GROUNDING SYSTEM AT BLDG 2) INSTALL REJECTION PINS IN SERVICE DISC. SWITCHES, INSTALL BOND SCREWS, LABELS 3) PERMIT TO REFLECT BOTH UNITS OR SPACES IN BLDG. ONE AND TWO 4) REVISE PLANS TO REFLECT ALL WORK |