Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) DO NOT SUPPORT CONDUIT OR CABLE MC FROM CONDUIT. SEC NEC ART 300.2.) DO NOT SUPPORT CABLE OR CONDUIT FROM WIRES WHICH WERE INSTALLED TO SUPPORT THE CIELING GRID. FURNISH SEPARATE WIRES FOR THIS PURPOSE. 3.) 2ND FLOOR ABOVE CEILING J BOX CONTAINS 3 ALUM. & 3 COPPER CONDUCTORS. SPECIAL MATERIALS AND SPLICING METHOD MUST BE USED TO SPLICE ALUM. TO COPPER. LEAVE THIS BOX EXPOSED AND UNCOVERED FOR FURTHER INSPECTION OF CONNECTIONS. |