Permit: T02CM01664

Parcel: 10510062H


Addresses:

620 E WETMORE RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM01664

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
11/10/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ CONDENSATE DRAIN, AIR HANDLER IN ATTIC OK.
05/07/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
04/25/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SPACE ABOVE RM. 305 5 TON AIR HAND. LER IN TRUSSES. HOW WILL ACCESS, FUTURE A/H REPLACEMENT, ETC. BE ACCOMPLISHED ?? IMC SEC. 306.3.
CONSULT ARCHITECT/FOR PROPER DIRECTION ENGINEER.
04/10/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTION ON 1ST & 2ND FLOOR RESTROOMS 101,103, 105,212. EXHAUST DUCT NOT CONNECTED.
PROVIDE SCREWS IN JOINTS ON EXHAUST DUCTS. CRIMPS ON EXHAUST DUCTS WHY NOT SAME DIRECTION AS AIR FLOW?