Permit: T02CM01664

Parcel: 10510062H


Addresses:

620 E WETMORE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM01664

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
01/20/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
01/06/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
11/20/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1] GAS SLEEVE AND PVC DRAIN AT BBQ AREA OK. 2] MECH. ROOM NOT QUITE READY. 3] REC'D LISTING FOR PRO PRESS. NEED INSTALLATION MANUEL.
10/24/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) REVIEWED PLAN AND INSPECTION HISTORY. NEED LETTER OF APPROVAL FOR 'PRO PRESS' COPPER MAINS. 2) ALL OTHER AREAS COMPLETE AND MAY BE COVERED. 3) PLEASE INSTALL PER PLAN. 4) DRAIN FOR POOL EQUIPMENT. OK TO COVER.
10/15/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
07/09/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000* 1)FIRST FLOOR PVC , PEX, CLOSET FLANGES ARE OK. 2) OK TO COVER WALLS. DON'T FORGET LISTING AND AUTH FOR "PRO PRESS"
06/16/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) 2ND FLOOR DWV PVC OK. 2ND FLOOR PEX-OK. CLOSET FLANGES-OK. TUBS-OK 2) OK TO COVER SECOND FLOOR
06/10/2003 PLUMBING - INTERMEDIATE Partial Approval 1) 3RD FLOOR NORTH WING SOUTH SIDE-OK, OK TO COVER
06/02/2003 PLUMBING - INTERMEDIATE Partial Approval 1) NORTH SIDE OF NORTH WING-OK 2) PEX, PVC, CLOSET FLANGES-OK 3) OK TO COVER THIS AREA
05/29/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) 3RD FLOOR PEX WEST WING COMPLETE 2) 3RD FLOOR WEST WING ONLY OK TO COVER WALLS ALL AREAS
05/07/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*3RD FLOOR PEX FROM #331,#320 SOUTH TO END OF CORRIDOR OK
2.) CLOSET FLANGES OK
3.) OK TO COVER.
05/05/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*THIRD FLOOR PVC DWV OK
CONTRACTOR TO REPLACE PLUMBERS TAPE WITH APPROVED STRAPPING.
2.) NEED TO CHECK PEX AND STRAPS 3RD FLOOR.
05/01/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) WATER TEST FOR SECOND FLOOR PVC DWV AND THIRD FLOOR TUB TEST OK
2.)CLOSET FLANGES 2ND FLOOR OK
3.) PEX WATER PIPING UP TO 220 & 225 OK
NEED TO SEE FROM THERE NORTH FOR REST OF WING.
4.) PROVIDE AUTHORZATION FOR THE USE OF "PROGRESS" COPPER FITTINGS.
04/30/2003 PLUMBING - INTERMEDIATE Partial Approval PVC DWV FROM FIRST FLOOR UP TO 2ND FLOOR OK WATER TEST TO 2ND FLOOR OK.
TUB TEST FOR 2ND FLOOR OK
PVC FOR ENTIRE FIRST TO 2ND FLOOR OK
2.) PEX APPROVED BY ARCHETECT. PEX PIPING TO ROOMS ONLY FIRST FLOOR OK TO COVER.
3.) ALL STRAPS TO BE APPROVED TYPE.
01/31/2003 PLUMBING - INTERMEDIATE Denied NOT INSTALLED PER PLAN
SEE 15,400 C-2 INTERIOR WATER LINES.
01/12/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) TUB FLOW TEST ON FIRST FLOOR OK
OK TO DROP TEST.
OK TO COVER.
11/27/2002 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*OFFICE LOCKED WILL NEED APPROVED PLAN & SPEC WILL NEED ARCH STAMP ON LETTER OF REVISION. SEE PLAN / FOR C O WILL NEED SPEC FOR WATER INSIDE.