Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM01664
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) WILL CHECK OUT 2/6/04 | |
01/23/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ FINAL NOT READY - OK FOR C OF O. | |
01/22/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK FOR TEMP C OF O. FOR FINAL FINISH OTHER ITEMS DICUSSED WITH ELECTRICAL CONTRACTOR. UNSHIELDED LIGHTS TO REMAIN OFF UNTILL INSPECTED. E-1 MAC CAPISTRAN TO GO OVER FINAL SINCE HE HAS BEEN THE INSPECTOR OF RECORD THRU MOST OF THE JOB. | |
01/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) REMOVE ALL STORAGE ITEMS FROM IN FRONT OF POOL PANEL. 2) ALL OUTSIDE LIGHTING TO 50 WATTS OR LESS UNSHIELDED. 3) PROTECT BBQ AREA WIRING. 4) KIT UNDERCABINET LIGHTING NOT IN, BOXES COVERED.5) BUSINESS OFFICE LIGHTS NOT IN BOX COVERED. 6) CONTRACTOR IN ELECT. ROOM TO BE FINISHED. 7) APPROX. 8 FIXTURE 1ST FLOOR ROOM NOT IN ABOVE SINK. 8) EM. LIGHT 1ST FLOOR REAR EXIT. 9) ALL AC UNITS TO HAVE GREEN BOND SCREWS SOME MISSING. 10) OUTSIDE SIGN LIGHTS MONUMENT FIXTURES NEED TO BE SUPPORTED RIDGIDLY. | |
01/20/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
01/14/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ PROGRESSING - ONGOING TEST OF ALL ELECTRICAL PLANT. | |
12/15/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 2ND FLOOR UNITS AND HALLWAYS WITH STAIRWELLS. | |
12/10/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) 3RD FLOOR GUEST ROOMS AND HALLWAYS |