Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE STUCCO CERT, INSULATION CERT - POST TENSION CERTIFICATE AND HAVE FIRE SPRINKLER FINAL & C OF O FIRE APPROVALS |
|
| 10/25/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) T & P RELIEF LINES NOT CONNECTED AND MUST BE HARD PIPED 2) SMOKE DETECTORS IN HALL NEEDS TO BE 36" AWAY FROM REGISTER UPSTAIRS 3) GFCI AT JACK AND JILL MUST BE 36" FROM LAV 4) S/E BEDROOM OPEN NEUTRALS 5) SW HALL UPSTAIRS NO POWER 6) LIGHT IN HALL CLOSET TO CLOSE TO COMBUSTIBLES |