Permit: T02CM01652

Parcel: 11931013C

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/18/2005 FRAMING Approved IVRS - Inspection :*
12/29/2004 FRAMING Partial Approval IVRS - Inspection :*
1) FIRE BLOCKS MISSING AT HIGH CEILING AND ENTRY INSULATION TO BE USED
2) HIGH CEILING LIGHTS TO BE WIRED WHEN SCAFFOLD INSTALLED
3) OK TO INSULATE
4) CALL FOR FIRE BLOCK AFTER INSULATION AND BEFORE DRYWALL
12/23/2004 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
You must have official original inspection card and proof of all prior inspections
Fire blocking missing at great room and entry
Fire stop missing at fireplace
Combustible material within 2" of fireplace "B" vent
Nail protect a/c copper at dark room
Ground all metal electric boxes
Provide patio door illation instructions
Door warped 2"
High ceiling lights not wired
Repair two leaks at plumbing and floor
Provide listing on fire suppression cross connection device
No change from 12/20/04 inspection
Stopped inspection
Too many items
12/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HANGER MISSING IN OFFICE
2) FIRE BLOCKS MISSING GREAT ROOM
3) FIRE STOP MISSING AT FIRPLACE/THROUGHOUT
4) COMBUSTIBLE MATERIAL WITHIN 2" OF FIREPLACE B-VENT
5) NAIL PROTECT A/C COPPER
6) NAIL PROTECT COPPER ? ROD
7) GROUND MEATAL BOXES
8) PATIO DOORS BOWED. PROVIDE MANUFACTURERS INSTALLATION MANUAL
9) HIGH CEILING LIGHTS NOT WIRED
10) LEAK LEFT DUEL BATH (2)
11) PROVIDE LISTING ON CROSS CONNECTION PRETENSION VALVE
12/10/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMIT
2) NO ACCESS
3) HOUSE LOCKED
4) DUE TO WORK LOAD CANNOT MAKE P.M. INSPECTION
11/22/2004 FRAMING Denied IVRS - Inspection :
There is no access to the site.| 920*/ 1) DANGEROUS ROAD-NO ACCESS TO SITE
11/15/2004 FRAMING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*/ 1) NO PLANS PERMIT OR PRIOR INSPECTION REPORTS ON SITE
2) NO VEHICLE ACCESS TO SITE. TRUCK BLOCKING ROAD. YOU MUST PROVIDE ACCESS TO SITE
3) NEXT FAILURE WILL BE CHARGED REINSPECTION FEE
11/12/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY PER ANDY
11/08/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY PER OWNER
10/15/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LAUNDRY MISSING HD BOLT, FB AND RED HEADS 2) SUPPORT 1/2" GAS LINE AT 6" ON CENTER 3) DRAIN LEAKS 4) TOILET VENT MUST ATTACH ABOVE CENTER LINE OF DRAIN CHECK ALL 5) FIRE BLOCKS MISSING THRU-OUT 6) BLOCK MECH BOOTS 7) F/P "B" 2" CLEARANCE AND FIRESTOP 8) MAKE UP ALL GROUNDS 9) GROUND ALL METAL ELECTRIC BOXES 10) STAIR RISE EXCEEDS 7 8/4" 11) PROVIDE MAX 30 PSI GAS GAUGE 12) WIRING NOT COMPLETE 13) LAV DIRTY ARM MORE THAN 42" AND 1 1/2" 14) CLIP TRUSSES AT BEARING PT 15) FHA STRAP PLATE CUTS 16) 36" GUARD RAILS REQUIRED 17) INSULATE DUCT "Y'S"
10/14/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
09/10/2004 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES 2) MAKE UP ALL GROUNDS AND CONNECT WITH A MECHANICAL FASTENERS 3) PROVIDE GROUND PIG TAILS FOR ALL SWITCHES AND OUTLETS 4) NO CITY OF TUCSON APPROVED PLANS ON SITE, ALSO INSPECTION CARD
07/23/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*