Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2002 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* 1.) ABS UNDERGROUND OK 2.) COPPER OK 3.) OK TO COVER FLOOR AND WALLS. 4.) GAS RE-ROUTED AND RETESTED OK 5.) REVIEW NOTES FROM HEALTH DEPT AND COMPLY, REVISE PLAN IF NECESSARY AND CALL IN INSPECTION FOR ALL RESULTING WORK. | |
06/20/2002 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1.) CAP OFF ABANDONED PIPING WITH APPROVED CAPS 2.) COPPER AND GALVANIZED MAY NOT BE DIRECTLY CONNECTED 3.) A FURNCO (UNSHIELDED) MAY NOT BE USED INSIDE OR UNDER BLDG. 4.) PROTECT COPPER WHERE PASSING THROUGH MASONRY 5.) WATER TEST FOR 3 COMP SINK, AND MOP SINK OK 6.) HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE THROUGH WYE BRANCH OR EQUILDENT. 7.) GAS SHALL BE A MINIMUM OF 12" BELOW GRADE. |