Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000*/ 1) NOTE: NEED TRUSS DRAWINGS, FIX TRUSS FROM LAST INSPECTION AND SECURE FRONT DOOR BOTTOM PLATE. WILL CHECK AT INTERMEDIATE |
| 05/17/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NEED TRUSS DRAWINGS (COMPLETE SET) 2) TRUSS REPAIR NOT PER DETAIL, NAIL BOTH SIDES OF GUSSET, NAIL PER SCHEDULE AND TRUSS T4B REQUIRES 3/4" OR 23/32 OSB EXPOSURE WITH SPAN RATING OF 48/24, YOU USED 1/2" OSB 3) FRONT DOOR BOTTOM PLATE STILL LOOSE |
| 05/15/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) STRAP ALL CORNERS NOT CABIN TIED 2) FINISH POP OUTS 3) NEED TRUSS REPAIR DETAIL (BROKEN TRUSSES) 4) NAIL BANG PLATES AT FRONT DOOR 5) TIE BAY WINDOW WALLS WITH STRAPING (ROLL) 6) COL. PLATE BOLTS 7) NAIL STUDS AT FRONT COLUMN TO WALL |