Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T02CM01598
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2002 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE OK FOR CEILING TILES. | |
05/22/2002 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) PROVIDE MIN 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINE. INSULATE AS PER PLANS. 2.) STRAP FLEX DUCT EVERY 4' W/ 1/2 WIDE STRAP. 3.) FINISH INSTALLING SUPPLY DIFFUSERS. 4.) INSULATE BARE METAL ELBOW & START COLLARS. SEAL AROUND START COLLARS RECALL FOR INSPECTION. | |
04/25/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*INSPECTION ON SUSPENDED ROUGH DUCT. SMOKE DETECTORS ARE OK OK TO PROCEED. |