Permit: T02CM01576

Parcel: 141013730


Addresses:

5149 S ZENITH WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM01576

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2003 FRAMING Approved IVRS - Inspection 0000*
01/23/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1ST FLOOR: 1) BANG PLATE ALL ABS. VENTS AND DRAINS AND DRYER VENT 2) BACKING FOR TUB SIDEWALLS 3) CONNECT ROMEX TO EXHAUSTFAN ABOVE TOILET 4) SOFFIT ON EAST WALL COMM. WIRE OUT OF WALL PLANS 5) NEED H.D. NEEDED AT SW4 PLATE PINS AND X BRACE TIE TOP PLATE TO FLOOR 2ND FLOOR: 1) MISSING SCREWS IN PLATES AT X BRACES NORTH EAST WALL BOTTOM PLATE 2) TUB BACKING 3) LIGHT FIXTURE IN CLOSETS TO BE 12" FROM SHELF IF IN CANDESANT, SIX INCHES IF RECESSED OR FLOURESCENT
11/12/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SECURE WATER LINES IN WALL CAVITY BETWEEN LAUNDRY AND MASTER WATER CLOSET 2) STAIRWAY RISER HEIGHTS NOT PER CODE. MAXIMUM RISER HEIGHT IS 7 3/4" AND MAXIMUM VARIATION IN RISER HEIGHT IS 3/8". MINIMUM TREAD WIDTH IS 10". SEE IRC SECTION 314 UNABLE TO VERIFY DWV TEST 4) INCOMPLETE ELECTRIC IN LR CEILING
10/24/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*
09/20/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FRAMING OK BUT WILL BE DONE WITH INTERMEDIATE INSPECTION GROUP