Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/01/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/28/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUND ALL METAL ELECTRIC BOXES 2) MAKE UP (CONNECT) ALL GROUNDS IN BOXES AND SECURE WITH APPROVED MECHANICAL FASTENERS 3) REVISE PLAN FOR BLOCKING RELOCATING DOOR TO KITCHEN 4) LAUNDRY WASHER MUST HAVE 2' DRAIN 5) LAUNDRY NOT TRAPPED OR VENTED 6) DRYER EXHAUST DUCT MUST EQUAL 4" DIAMETER VOLUME 12 1/2 SQUARE INCHES. FLEX DUCT NOT ALLOWED 7) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES AND BE SECURED WITHIN 8" WITH SHEATHING 1/4" IN BOX 8) LAUNDRY ROMEX CLAMP LOOSE DRYER 9) FIREBLOCK TOP PLATE OF EAST WALL AT MASONRY 10) INADEQUATE LIGHT IN VENT IN REC ROOM PROVIDE ENVIORMENTAL ENGINEER CERTIFICATION OR IRC COMPLIANCE 11) BEARING WALL NOT ANCHORED PER PLAN. 2 RAM SETS IN EACH PLATE 12) REVISE PLAN FOR ROCKET DOORS 13) CLIP TRUSSES WITH H2.5 TO BEARING WALL 14) EXISTING BATHROOMS REQUIRE EXHAUST FANS 15) BLOCK DEFUSER BOOTS 3 SIDES 16) REVISE ALL PLANS TO AS BUILT |