Permit: T02CM01536

Parcel: 103090770

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/04/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
11/19/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*PLEASE OPEN CEILING TILE AS DISCUSSED FOR INSPECTION.
11/15/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
11/14/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PLEASE ATTACH FIXTURES TO GRID.
2.) PROVIDE WORKING CLEARANCE AT A/C DISCONNECT AH-4,AH-8,
3.) RECESSED CANS NEED SUPPORT WIRES.
4.) ELECTRIC TO BE INDEPENDENTLY SUPPORTED 300-11.
5.) SUPPORT WIRES TO BE OPPOSITE ATTACHMENT PLEASE BOND FOUNTAIN.
08/29/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*