Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
| 11/26/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*STRAP WATER HEATER FLEX CORRECT. 2.) BOND GUTTER ENCLOUSER. 3.) BONDING JUMPER TO PER AS PER 250-102. 4.) CANNOT STACK LUGS. 5.) TIGHT LOOSE TERMANAL IN MIDDLE DISCONNECT. 6.) WE HAVE EXPOSED CONDUCTORS AT FUTURE PANELS. 7.) A GFI PROTECTED RECEPTICAL IS NEEDED WITH IN 25' OF UNITS 8.) PLEASE MAINTAIN WORKING CLEARENCE IN FRONT OF BOX. 3.) BONDING JUMPER TO PER AS PER 250-102 4.) CANNOT STACK LUGS. 5.) TIGHT LOOSE TERMANAL IN MIDDLE DISCONNECT 6.) WE HAVE EXPOSED CONDUCTORS AT FUTURE PANELS. 7.) A GFI PROTECTED RECEPTICAL IS NEEDED WITH IN 25' OF UNITS. 8.) PLEASE MAINTAIN WORKING |
|
| 10/25/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) GROUND BUSHINGS REQUIRED AT SERVICE AREA ANYWHERE THERE ARE UP PROTECTED CONDUCTORS. 2.) ADDRESS ON SERVICE MUST BE 149 W SAHUARO. 3.) WATER BOND OK 4.) PANEL A MISSING FILLER. 5.) MISSING WATER HEATER ELECT. 6.) OUTSIDE EITHER CONNECT IRRG GFI OR SEAL. 7.) NEED TO CHECK ROOF FOR AC DISCONN & GFI. WILL VERIFY ON NEED OF FUTURE SERVICES. OWNER TO SUBMIT A PLAN FOR EXTRA SERVICES ON PANELS. |