Permit: T02CM01511

Parcel: 110065580

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM01511

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/17/2002 FRAMING Approved IVRS - Inspection 0000*
05/16/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE TOP PLATE BLOCKING FOR GARAGE SOUTH SHEAR WALL #1 2) SHOWER NOT VENTED (SEE PLAN) 3) BEDROOM 2 SHEAR WALL 2 MISSING SHEAR BLOCKS 4) LAUNDRY DRYER WIRE TRAPPED-DAMAGED 5) SILL PLATE NORTH OF ENTRY MISSING ANCHOR BOLTS 6) FIRE BLOCK MISSING SOUTH OF PATIO DOOR AND MASTER BEDROOM 7) FIREPLACE OFFSET ELBOW NOT FULLY STRAPPED 8) STUD MISSING OVER SPAN AT HALL CLOSET 9) SUPPORT WIRES AT 4' ON CENTER AND AT SERVICE