Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/20/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK TO BACKFILL TRENCH. |
| 05/16/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
1.) MUST USE L SWEEPS ON FLAT VENT SYSTEM 2.) MUST USE BELL REDUCES ON ALL HORIZONTAL WASTE LINES. 3.) MUST USE DOUBLE FIXTURE FITTINGS FOR LAVATORYS. 4.) MIN TRAP ARM SIZE IS TWO TIMES THE PIPE DIAMETER FO DRAIN LINES USED FOR MOP SINK 5.) RE TEST SYSTEMS. |