Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM01508
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2002 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) WASTE & VENT SYSTEM IS OK 3.) OVERHEAD WATER DISTRIBUTION IS OK 4.) OK FOR DRYWALL. | |
04/10/2002 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) WASTE & VENT SYSTEM REQUIRES WATER TEST ALL THE WAY TO ROOF. 2.) VENT SYSTEM IS OVERLOADED ON FIXTURE UNITS. APPROVED PLAN CALLS FOR 3" VTR. 3.) CLOSET RINGS NOT INSTALLED. |