Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/11/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) WASTE & VENT SYSTEM IS OK 3.) OVERHEAD WATER DISTRIBUTION IS OK 4.) OK FOR DRYWALL. |
| 04/10/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |