Permit: T02CM01481

Parcel: 115170160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 10/1/02 AT 9:15 AM.
09/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*WAITING ON LETTER FOR ARC-FAULT BREAKRES.
09/24/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*CANCEL BY OFFICE.
09/20/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE FINISH ITEMS #3,4,7,& 13 OF PREVIOUS INSPECTION.
09/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1. PLEASE SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE.
2. PERMANENT METAL ADDRESS LABLES ARE NEEDED.
3. SPLIT BOLTS ARE LISTED FOR ONLY A RUN AND ATAP- 2 CONDUCTORS.
4.) PLEASE ARRANGE TAPS SO AS NOT TO PUSH ON COVER.
5.) FINISH MAKE UP OF CONDUCTORS IN PANEL
6.) INSTALL NEUTRALS AS PER MANUFACTURES INSTRUCTIONS
7.) BREAKERS WILL NEED TO BE LABELED.
8.) TIGHTEN SEALTITE FITTINGS IS NEEDED AT HOOD.
9.) AN APPROVED CONNECTOR IS NEEDED AT HOOD.
10.) FINISH GARBARGE DISPOSAL PLUG.
11.) LIGHT OVER WASHER/DRY OK ALSO USE AN APPROVED CONNECTOR.
12.) MAINTAIN WORKING CLEARENCE AT A/C DISCONNECT.
13.) PLEASE INSTALL ARC FAULT BREAKERS AS PER PLANS OR REVISE PLANS.