Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 04/02/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) ELECTRICAL WIRING TO BE SUPPORTED BY INDEPENDANT MEANS 300-11. 2.) FIXTURES TO BE ATTACHED TO GRID. 3.) DATA LAYING ON GRID. 4.) M/C FITTINGS TO BE TIGHTENED. |