Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM01461

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/03/2002 ELECTRIC - ABOVE CEILING Approved
04/02/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*1.) ELECTRICAL WIRING TO BE SUPPORTED BY INDEPENDANT MEANS 300-11. 2.) FIXTURES TO BE ATTACHED TO GRID. 3.) DATA LAYING ON GRID. 4.) M/C FITTINGS TO BE TIGHTENED.