Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02CM01460

Parcel: 117200290


Addresses:

260 S CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM01460

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/10/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*EMT MUST BE SUPPORTED WITHIN 3' OF TERMINATION AND AT 10' INTERVALS PER NEC.