Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T02CM01439
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2002 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* OK TO POUR. | |
07/18/2002 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*1.) CLEAR DISTANCE BETWEEN ADJACENT REINFORCING BARS MUST BE 1BD MINIMUM BUT NOT LESS THAN 1" PER ACT 318 AND IBC. 2.) COMPACTION REPORT REVIEWED & ACCEPTED. |