Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T02CM01438
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2002 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection 0000*1.) 4" ABS BLDG SEWER FROM 2 WAY CLEAN OUT TO TIE-IN OK 3.) TRANSITION FITTING OK 3.) OK TO COVER. | |
05/19/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*1) REVIEWED REVISED APROVED PLAN. 2.) REVIEWED LETTER FROM FREDRICK RLS (SURVEYOR) DOCUMUTING INVERT IF MANHOLES. | |
05/10/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*TEST FROM M-H #2 TO M-H #3 TEST OK REVISED PLAN ON JOB RICK WILL LOOK AT THIS AT TIME OF NEXT INSP VACUUM TEST REQUIRED ON M-H #3. PROVIDE VARIFICATION OF GRADE AT TIME OF NEXT INSP. | |
05/03/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*1.) ALL PIPING FROM MANHOLE #1 TO MANHOLE #2 INCLUDING HCS CONNECTIONS INSPECTED BY PIMA COUNTY WASTEWATER. THIS INSPECTION IS FOR AREA NOTE AS PRIVATE SEWER ONLY INCLUDING HCS CONNECTION BETWEEN MANHOLE #2 AND MANHOLE #3. PROVIDE VERIFICATION OF GRADE BY ENGINEER AIR TEST AT LATER DATE SECURE REVISED APPROVED PLAN FOR ADDITIONAL HCS CONNECTIONS. |