Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2002 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
07/17/2002 | BUILDING PRE-SLAB | Not ready for Inspection | IVRS - Inspection 0000*1.) PATTISON EVANOFF GAS VERBAL COMPACTION RESULTS OF 96% & 98%. 2.) SPECIAL INSPECTION REPORT NOT READY. 3.) DETAIL 2 X 51.5 CALLS FOR #3 HAIRPINS #@ DEAD ENDS OF TENDONS CONTRACTOR HAS USED 2-#4 CONTINUOUS INSTEAD OK IF 1" MINIMUM SEPERATION BETWEEN T & B MAINTAINED. 4.) DETAIL ON X 51.5 CALL FOR TERMINAL ENDS OF TENDONS TO BE 5 1/2" BELOW T; MOST ARE ONLY 4 1/2. I NEED ENGINEER OF RECORD TO LET ME KNOW IF THIS IS WITHIN TOLERANCES. |