Permit: T02CM01423

Parcel: 11310026B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM01423

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2002 ELECTRIC - ABOVE CEILING Approved
04/03/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NOTES 1.) RE-WRITE PANEL SCHEDULE IN A LEDGIBLE MANNER. 2.) PLUG KO'S ON PANEL DEADFRONT. 3.) REMOVE PANEL DEAD FRONT TO VERIFY HOME RUN CIRCUITS, IT APPEARS CONTR. TRIED TO COMBINE TO MANY CONDUCTORS IN AN EXIST. CONDUIT, SEE NOTES ON PLAN. 4.) REMOVE ALL TILES ASSOCIATED WITH WORK DONE ABOVE CEILING.
04/02/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
03/31/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
03/28/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*