Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM01413
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
03/27/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) ELECTRIC OUTLET REQUIRED WITHIN 6 FEET OF THE WEST SIDE OF ENTRY DOOR. TO ROOF 2) ELECTRIC OUTLETS CANNOT BE GREATER THAN 12 FEET APART ONE ADDITIONAL NEEDED ON SOUTH WALL 3) EGRESS FOR BEDROOM DOES NOT MEET MINIMUM REQUIREMENTS. WEST WINDOW IS OF ADEQUATE SIZE BUT SILL IS 48" HIGH MAXIMUM ALLOWED IS 44"-SOUTH WINDOW SILL IS 40" AND OPENING WIDTH IS 20 1/4" BY 32 3/4"=4.72 SQ. FT. MINIMUM ALLOWED IS 5.7 SQ. FT. 4) BEDROOM (INCLUDING EXISTING BEDROOMS) MUST HAVE AT LEAST BATTERY OPERATED SMOKE DETECTORS 5) LABEL ALL CIRCUITS IN ELECTRIC PANEL |