Permit: T02CM01354

Parcel: 136192090

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM01354

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/13/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
1.) SOIL WATER TEST IS OK
2.) OVERHEAD WATER DISTRIBUTION
3.) OK TO DRYWALL.
02/12/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1. CAN NOT USE NO HUB COUPLING WHEN CONNECTING ABS TO C.I. MUST USE SPECILATY COUPLINGS.
2.) P-TRAP MAX HEIGHT FOR A.W. CAN ONLY BE 18" A.F.F. 804.1 94 UPC.
3.) P-TRAP FOR A.W. @ NORTH UNIT DOSE NOT HAVE MIN TRAP ARM DISTANCE 1002.2. 94 UPC
4.) MUST PROVIDE METAL OR FIRE RATED CATCH A DRIP BOX FOR A.W. IN FIRE WALL.
5.) CAN NOT USE A 2" TRAP ARM FOR LAVATORY 1003.3. 94UPC
6.) MUST PROVIDE WATER TEST ON WASTE & VENT
7.) APPROVED DRAWING INDICATE TYPE (L) COPPER FOR WATER DISTRIBUTION.
8.) PLAN SHOWS 1 1/4 TO FEED WATER HTR.