Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM01354
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) SOIL WATER TEST IS OK 2.) OVERHEAD WATER DISTRIBUTION 3.) OK TO DRYWALL. |
|
| 02/12/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1. CAN NOT USE NO HUB COUPLING WHEN CONNECTING ABS TO C.I. MUST USE SPECILATY COUPLINGS. 2.) P-TRAP MAX HEIGHT FOR A.W. CAN ONLY BE 18" A.F.F. 804.1 94 UPC. 3.) P-TRAP FOR A.W. @ NORTH UNIT DOSE NOT HAVE MIN TRAP ARM DISTANCE 1002.2. 94 UPC 4.) MUST PROVIDE METAL OR FIRE RATED CATCH A DRIP BOX FOR A.W. IN FIRE WALL. 5.) CAN NOT USE A 2" TRAP ARM FOR LAVATORY 1003.3. 94UPC 6.) MUST PROVIDE WATER TEST ON WASTE & VENT 7.) APPROVED DRAWING INDICATE TYPE (L) COPPER FOR WATER DISTRIBUTION. 8.) PLAN SHOWS 1 1/4 TO FEED WATER HTR. |