Permit: T02CM01323

Parcel: 114540650

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/30/2002 PLUMBING - INTERMEDIATE Approved
04/08/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1. WASTE & VENT SYSTEM IN WALLS IS OK 2.) OVERHEAD WATER DISTRIBUTION IS OK 3.) OK TO DRYWALL. 4.) NOTE: ZIP STICK IS NOT ACCEPTABLE MATERIAL FOR CAST IRON. PROVIDE CLEVIS HANGERS OR PROVIDE LISTING ON ZIP STICK AS REQUESTED. 5.) CLOSET RING INSTALLATION IS OK.
04/05/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) CLOSET RING NOT INSTALLED 2.) 1/2" COPPER IS TOUCHING 1" COLD SUPPLY FOR WATER HTR. 3.) PROVIDE LISTING FOR ZIP STICK HANGERS ON HORIZONTAL 2" VENT FOR C.I. APPLICATION. 4.) APPROVED PLAN CALLS FOR SELF PRIMING TRAP. THIS SOUNDS LIKE A TRAP PRIMER TO ME?
03/25/2002 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*