Permit: T02CM01323

Parcel: 114540650

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
04/24/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) IF NO BOND POSTED FOR TEMP POWER THEN AFTER FINAL APPROVAL OF MECH AND PLUMBERING AND OK FROM BLD INSPECTOR, A RELEASE FOR POWER CAN BE ISSUED. RE CALL FOR ELECTRIC FINAL WHEN ALL THE ABOVE IS COMPLIED WITH.
04/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) ALL DEVICES TO BE PIGTAILED TO BOXES PER 250-148A,370-40D N.E.C. 2.) SECURE 2 X 4 LAY IN LIGHT FIXTURES TO GRID WITH #8 SCREWS OR BEND OUT CLIPS ON FIXTURES 3.) SUPPORT EMT CONDUIT WITHIN 3' EACH BOX PER 348-13 NEC.