Permit: T02CM01291

Parcel: 107081370


Addresses:

837 W TIPTON DR

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/03/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*FINISH ITEMS #8,11,12,14,15, AND HAVE LICENSE C-11. CONTRACTOR CONTACT OFFICE BEFORE NEXT INSPECTION.
03/12/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) PANEL COVER TO BE SCREWED ON PROPERLY. 2.) REMOVE DOUBLE LUGGING AT #3 CIRCUIT BREAKER. 3.) #2 CIRCUIT BREAKER CONDUCTORS AND CIRCUIT BREAKER. 4.) GROUND PANEL ENCLOSURE TO GROUND OUT NEUTRAL BAR 5.) CORRECT IMPROPER SPLICE IN PANEL. 7.) 1" PVC GOING INTO SIDE OF PANEL HAS NO LOCK NUT 8) ADDRESS SERVICE PERMANENTLY NO MARKER. 9.) TEP OVERHEAD LINE IS REQUIRED AT SERVICE TO BE WEATHERPROOF 11.) RECEPTACLES BY KITCHEN SINK AND BATHROOM SINK TO BE GFI PROTECTED. 12.) SMOKE DETECTOR IN BEDROOM ARE REQUIRED BATTERY OK MUST BE 3' FROM SUPPLY OR RETURN AIR AND 9-12" BELOW CEILING 13.) FIX RECEPTACLE ABOVE RERIGERATOR. 14.) CLOSET WHERE PANEL INSTALLED CORRECT SWITCH INSTALLATION, PANEL HAS BEEN INCORRECTLY INSTALLED 2 FEEDS CANNOT TELL WHERE THE ORIGINAL DUE TO WIRE SIZE. 15.) FIXTURE AT FRONT DOOR INCORRECTLY INSTALLED. YOU NEED TO OBTAIN A C-11 ELECTRICAL CONTRACTOR TO CORRECT THESE PROBLEMS PLEASE CALL ME OR HAVE YOUR ELECTRICIAN CLAL ME SINCE HOME NOT OCCUPPIED YO NEED ELECTRICIAN.