Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T02CM01282
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) WASTE AND VENT SYSTEM WATER TEST OK 4) OK FOR DRYWALL | |
05/30/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1) MUST TEST GAS SYSTEM IN ITS ENTIRETY 2) MUST LOCATE HANGERS FOR OVERHEAD WATER DISTRIBUTION EVERY 6' -0'' 3) WASTE & VENT SYSTEM IS OL WATER TEST OK 4) MUST INSTALL ROOF SACKS FOR ALL ROOF PENETRATIONS. 5) NO CLOSET RINGS. | |
05/28/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION | |
05/23/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
05/23/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NOT READY ON WASTE AND VENTS NO TEST HANGERS MISSING. PLEASE NOT HANGERS REQUIRED 4' FOR ABS 2) PROVIDE MID STORY ANCHORS ON ALL ABS AND COPPER WATER PIPING 3) PLEASE SEE SPECS FOR INSULATION ON WATER LINES 4) CODE VIOLATION ON ANSOL VALVE HAVE PLUMBER ON JOB AT TIME OF NEXT INSPECTION |