Permit: T02CM01282

Parcel: 132191160

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T02CM01282

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2003 PLUMBING - ROUGH, SOIL Approved 1.) SOIL WATER TEST IS OK
2.) ALL CORRECTION HAVE BEEN MADE.
01/29/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) SPECS ON PLAN CALLS FOR PVC SCHEDULE 40 UNDERSLAB FOR WASTE AND VENT SYSTEM 2) CAN NOT USE CAST IRON, NO HUB COUPLING WHEN CONNECTIONS DISSIMULAR MATERIAL 3) CAN NOT USE FERNCO COUPLING WITHIN THE STRUCTURE 4) CAN NOT HAVE TEST WYE WITH REVERSED FLOW 5) CAN NOT USE A FLAT FACED BUSHING IN A HORIZONTAL POSITION 6) S-3 CALL FOR A 3" WASTE LINE 7) GREASE TRAP REQUIRES A VENT 8) CLEANOUT FOR GREASE TRAP MUST BE L-SWEEP 9) CAN NOT HAVE A HORIZONTAL VENT BELOW 6" OF FLOOD RIM LEVEL FOR S-3 10) CAN NOT USE 1/4 BEND FOR FLAT VENT 11) FLAT VENTS MUST BE ABOVE THE CENTER LINE OF FLOW 12) MAKE SURE WATER TEST IS UP ON ENTIRE SYSTEM, RELEASE AIR IN LINES