Permit: T02CM01282

Parcel: 132191160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM01282

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) CLEARANCE SUBJECT TO SIGN OFF BY ALL INSPECTORS
09/09/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ SUITE '120' ON PERMIT DOES NOT MATCH THE '110' AT FRONT DOOR OR ON METER BASE. MAKE APPROPRIATE CORRECTION AND RECALL.
09/05/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000* NO INSPECTION AT SITE. NOT READY. CALLED ELECTRICAL CONTRACTOR . CONTRACTOR TO CALL WHEN READY.
09/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* PLEASE COMPLY W/ALL OF THE ABOVE AND RECALL INSPECTION. CHANGE PERMIT TO REFLET UNIT 110
08/27/2003 ELECTRIC - FINAL Denied * HOOD SYSTEM FIELD INSTALLED LIGHTING REQUIRES HIGH TEMP. WIRING I.E. 105 DEGREE C.
* 400 AMP DISCONNECT DOOR IN VIOLATION OF NEC 110-26 ( '99 NEC ) - 6-1/2 FT MIN. HT AT 3 FT OUT OF FRONT OF DISCONNECT. * ADDRESS CORRECTION REQUIRED FOR SUITE NO. ALSO AFFIX PERMANENT SUITE NUMBER TO METER BASE ADDRESS. * OPEN SUB PANEL. * NEED A/C O.C. PROTECTION PER DATA TAG. * OPEN CEILING FILTER.