Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM01282
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) CLEARANCE SUBJECT TO SIGN OFF BY ALL INSPECTORS | |
09/09/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ SUITE '120' ON PERMIT DOES NOT MATCH THE '110' AT FRONT DOOR OR ON METER BASE. MAKE APPROPRIATE CORRECTION AND RECALL. | |
09/05/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* NO INSPECTION AT SITE. NOT READY. CALLED ELECTRICAL CONTRACTOR . CONTRACTOR TO CALL WHEN READY. | |
09/04/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* PLEASE COMPLY W/ALL OF THE ABOVE AND RECALL INSPECTION. CHANGE PERMIT TO REFLET UNIT 110 | |
08/27/2003 | ELECTRIC - FINAL | Denied | * HOOD SYSTEM FIELD INSTALLED LIGHTING REQUIRES HIGH TEMP. WIRING I.E. 105 DEGREE C. * 400 AMP DISCONNECT DOOR IN VIOLATION OF NEC 110-26 ( '99 NEC ) - 6-1/2 FT MIN. HT AT 3 FT OUT OF FRONT OF DISCONNECT. * ADDRESS CORRECTION REQUIRED FOR SUITE NO. ALSO AFFIX PERMANENT SUITE NUMBER TO METER BASE ADDRESS. * OPEN SUB PANEL. * NEED A/C O.C. PROTECTION PER DATA TAG. * OPEN CEILING FILTER. |