Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/23/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER. 2.) AN EXTENDER RING IS NEEDED UNDER SINK AT GARABLE DISPOSAL. PLEASE USE AN APPROVED RING. METAL IS NOT APPROVED. 3.) BOND JUNCTION BOX ENCLOUSER 250-148. 4.) SPLICES TO EQUAL INSULATION THICKNESS 110-14. 5.) 1/4" MININUM HARD WARE IS NEEDED AT RISER. 6.) SUPPORT CONDUIT SLEVE TO JUNCTION BOX 7.) PLEASE LABEL BREAKERS. |