Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM01237
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/29/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
04/26/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NAIL PROTECT PEX WITHIN 1 1/2" OF STUD SURFACE 2) BEARING STUDS NOTCHED GREATER THAN 25 PERCENT-REPLACE (2) 3) PLUMBING NOT COMPLETE-LEAKS 4) PEX CANNOT BE WITHIN 12" OF RECESSED LIGHTS 5) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE (HALL CLOSET CORNER) |