Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM01229
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/08/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE USE CRIMP TYPE WIRING TERMINALS FOR STANDED CONDUCTOR TERMINATING OR DEVICE SCREWS. 2.) OVERFILL OF JUNCTION BOXES IN CASH WRAP AREA. 3.) MOVE GFCI RECEPTS SUPER JACENT TO SINK. 4.) NEED PROPER CLEARANCE IN FRONT OF PANEL PP. 5.) NEED CIRCUIT DIRECTION IN PANEL BROAD. | |
10/01/2002 | ELECTRIC - FINAL | Partial Approval | OK FOR TEMP C OF O FOR STOCKING AND MERCHANDISING |