Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/07/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF PERMITS FOR ELECTRICAL SERVICE PANEL REPLACEMENT/UPGRADE 2) PROVIDE PERMIT/PROOF INSPECTION FOR NEW MECHANICAL UNIT AND DUCT WORK 3) GROUNDED OUTLET IS UNGROUNDED BY CLOTHES WASHER 4) KITCHEN HAS BEEN REMODELED. ELECTRIC OUTLET RIGHT OF RANGE HAS HOT NEUTRAL REVERSED MUST BE GFCI PROTECTED 5) LABEL ALL CIRCUITS IN ELECTRIC PANEL 6) WEST BEDROOM APPEARS TO BE BUILT W/O PERMITS REQUIRES ELECTRIC OUTLETS WITHIN 6' OF DOOR AND EVERY 12' THERE AFTER, ALSO LIVING ROOM 7) BAR BULB LIGHT FIXTURES NOT ALLOWED IN CLOSETS 8) WEST BEDROOM HAS INADEQUATE EGRESS 9) BATHROOM GFCI OUTLET LOOSE 10) NORTHEAST BED ROOMS HAVE OBSTRUCTED GROUNDS |