Permit: T02CM01211

Parcel: 133095180

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM01211

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2002 FRAMING Approved IVRS - Inspection 0000*
05/29/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) DRYER VENT DUCT IS TO LONG 2) BEARING STUDS ARE OVER NOTCHED 3) SHIM HEADERS WHERE NEEDED 4) NAIL TJI BRACKETS UNDER STAIRS 5) HEADER OFF CUT STUD AT DUCT BOOT INSIDE FRONT DOOR 6) MOVE OUTLET ON STAIRS TOWARDS DOOR 7) CUT MASTER SOUTH WALL TOP PLATES TO ALLOW TRUSS CLEARANCE 8) REMOVE COMBUSTIBLES FROM BOTH FURNACE FLUES