Permit: T02CM01202


Addresses:

1951 N WILMOT RD 05


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T02CM01202

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2002 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection 0000*SENT TO TEP ON 11/26/02 AT 9:15AM PANEL OK TEC. SUBJECT TO LETTER ON TORQUE OF SERVICE INSTALL FUSES "J"
11/22/2002 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0245*SEE NOTES INSP. WRITE UP 11-19-02
11/19/2002 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0245*NEED TO VERIFY WATER & GAS BONDING TO SERVICE. 2.) HAVE CONTR. ON SITE TO REMOVE SES COVERS FOR INSPECTION OF FEEDER CONNECTIONS, BONDING, AND PROVIDE LETTER OF TORQUE FOR BUSINESS.
3.) MAKE UP OR CAP OFF BRANCH CIRCUIT HOME RUNS.