Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/14/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*CORRECTION MADE OK WATER TEST OK 2.) OK TO COVER. |
| 06/12/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) CAN NOT HAVE A FLAT FACED BUSHING ON HORIZONTAL DRAINAGE MUST USE A BELL REDUCER 2.) RE-TEST SYSTEM. |
| 06/11/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) ROUGH PLBG. WATER TEST WAS DOWN. 2.) CAN NOT HAVE ANY THREADED JOINTS UNDERSLAB REMOVE C.O. TEE AND USE WYE FOR TEST FITTING. |
| 05/30/2002 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OK TO BACKFILL TRENCH. |
| 05/29/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*MUST PROVIDE WATER TEST ON NEW BLDG. DRAIN WITH 10' HEAD. |