Permit: T02CM01187

Parcel: 126042120


Addresses:

4349 E 5TH ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/14/2002 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*CORRECTION MADE OK WATER TEST OK 2.) OK TO COVER.
06/12/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) CAN NOT HAVE A FLAT FACED BUSHING ON HORIZONTAL DRAINAGE MUST USE A BELL REDUCER 2.) RE-TEST SYSTEM.
06/11/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) ROUGH PLBG. WATER TEST WAS DOWN. 2.) CAN NOT HAVE ANY THREADED JOINTS UNDERSLAB REMOVE C.O. TEE AND USE WYE FOR TEST FITTING.
05/30/2002 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) OK TO BACKFILL TRENCH.
05/29/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*MUST PROVIDE WATER TEST ON NEW BLDG. DRAIN WITH 10' HEAD.