Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/12/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1.) MC CABLE WHEN BUNDLED TOGETHER MORE THAN 2' MUST BE DE RATED NEC. PER 310-15. 2.) MC TO BE SUPPORTED WITHIN 12" EACH TERMINATION PER 334-10 NEC. |
| 07/31/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* NOTES OK CONDUITS ON ROOF FOR AC UNIT & EXTERIOR LTG. |
| 07/23/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK WALLS ONLY INTERIOR & OUTER. |
| 06/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK BRANCH CIRCUIT CONDUITS UNDERSLAB. NOTE THAT J-BOX FOR BRANCH CIRCUITS UNDER EXISTING STRUCTURE MUST BE ACCESSABLE. |
| 05/28/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK UFER. |