Permit: T02CM01187

Parcel: 126042120


Addresses:

4349 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/13/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/12/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) MC CABLE WHEN BUNDLED TOGETHER MORE THAN 2' MUST BE DE RATED NEC. PER 310-15. 2.) MC TO BE SUPPORTED WITHIN 12" EACH TERMINATION PER 334-10 NEC.
07/31/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* NOTES OK CONDUITS ON ROOF FOR AC UNIT & EXTERIOR LTG.
07/23/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ONLY INTERIOR & OUTER.
06/11/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK BRANCH CIRCUIT CONDUITS UNDERSLAB. NOTE THAT J-BOX FOR BRANCH CIRCUITS UNDER EXISTING STRUCTURE MUST BE ACCESSABLE.
05/28/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK UFER.