Permit: T02CM01101

Parcel: 115220770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/09/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*DUE TO INSTALLATION METHOD THIS TIME ONLY CAN THE EXTENDER RINGS BE USED.
09/06/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0935*1.) IDENTIFY UNGROUNDED CONDUCTORS AS PER CODE AT WATER HEATER SWITCH. 2.) AN APPROVED FITTING IS NEEDED AT HOOD. 3.) AN APPROVED EXTENDER RING IS NEEDED WHEN MORE THAN 1/8" TO BOX EDGE FROM SURFACE. 4.) #6 PREVIOUS INSPECTION. 5.) TIGHTEN SEALTITE FITTINGS 6.) OUTLETS TO BE WEATHER PROOF WHEN PV USE 410-57.
09/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
08/30/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) COMPLETE #4 OF DATED 7-17-02 2.) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER ALSO TIGHTEN LOOSE FITTINGS 3.) AN APPROVED FITTING IS NEEDED FOR NM CABLE AT HOODS 373-5. 4.) A LIGHT FIXTURE IS NEEDED FOR LIVING ROOM 210-70. 5.) SWICHES TO BE GROUNDED 380-9. 6.) CLEARENCE TO LIVE PARTS SCREWS I METAL BOXES 7.) INSTALL BATH BAR AS PER CODE AND MANUFACTURES REQUIREMENTS 8.) SEAL AROUND OUTSIDE LIGHT BOXES TO MAKE WEATHER PROOF. 9.) WETHER PROOF COVERS ARE NEEDED FOR OUTSIDE RECEPTACLES WASH & DRYER. 410-57. CK ROOF NEXT TIME.