Permit: T02CM01101

Parcel: 115220770

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/01/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000* OK ROUGH ELECTRICAL
07/31/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) AN APPROVED CONNECTOR WILL BE NEEDED AT BATH LIGHT BOX AND PLEASE MAKE UP BOX. 2.) PLEASE PROTECT CABLE AT ENTRANCE TO FLEX. 3.) GROUNDS TO BE INSTALLED IN A CLOCKWISE DIRECTION UNDER SCREWS 4.) TIGHTEN ROMEX CONNECTORS TO CABLES AT PANEL.
07/25/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999* PLAN CALLS FOR 1/0 COPPER FEEDS WITH A 150AMP MAIN AT SERVICE AND A150AMP MAIN IN PANEL THE #2 AL = 100 AMPS (BOTH) AC CIRCUIT ON PLAN SHOWS TO AMP 2 POLE CB-#8 RUN TO AC GOOD FOR 50 AMPS (BOTH).
3.) INSTALL FLEX ON WH ROMEX AND STRAP TO STUB TO BE INSPECTED PRIOR TO DRYWALL. 4.) RECEPTACLE ON CIR 16 ON SM WALL FROM KIT SIDE NOT IN. 5.)INSTALL CARD BOARD COVER ON PNLS. 6.)INSTALL A BOX FOR BATH WALL MOUNT LIGHT OR WILL NEED TO VERIFY INSTALLED FIXTURE OK FOR BACK SIDE ROMEX ENTRY. REAR 1.) DRYER BOX EXTENDS OUT TOO MUCH. 2.) FLEX WH FEED, AND STRAPT TO STUD 3. SAME AS #4 ABOVE 4.) SAME AS #5. 5.) SAME AS #6. 6.) STAPLE THEROSTAT WIRE ABOVE CEILING BATHROOM